Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

    GV3ME63 Product picture
    Discontinued

    GV3ME63 Product picture
    Discontinued

    motor circuit breaker GV3-ME - 40..63 A - screw clamp terminal - thermomagnetic trip unit

    Show more characteristics >

    GV3ME63 is replaced by the following group of products:
    Add Product Group to Favorites Remove from My Favourites
    • Reason for substitution: End of life
    • Substitution date: 30 December 2008
    Or GV3ME63 may be replaced by any of the following products:
    Product
    Qty
    GV3P65
    Qty
    1
    Add to My Favourites Remove from My Favourites
    • Reason for substitution: End of life
    • Substitution date: 30 December 2008
    GV3P50
    Qty
    1
    Add to My Favourites Remove from My Favourites
    • Reason for substitution: End of life
    • Substitution date: 30 December 2008
    GV3P50
    Qty
    1
    Add to My Favourites Remove from My Favourites
    • Reason for substitution: End of life
    • Substitution date: 30 December 2008
    • Main
      range
      TeSys
      product name
      TeSys GV3
      device short name
      Thermal magnetic circuit breaker
      product or component type
      Circuit breaker
      device application
      Motor
      poles description
      3P
      network type
      AC
      control type
      Push-button
      motor power kW
      22 kW at 400...415 V AC 50/60 Hz
      30 kW at 400...415 V AC 50/60 Hz
      30 kW at 500 V AC 50/60 Hz
      37 kW at 500 V AC 50/60 Hz
      37 kW at 660...690 V AC 50/60 Hz
      45 kW at 660...690 V AC 50/60 Hz
      trip unit technology
      Thermal-magnetic
      utilisation category
      AC-3 conforming to IEC 60947-4-1
      Category A conforming to IEC 60947-2
      connections - terminals
      Power circuit : screw clamp terminal 1 cable 2.5 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw clamp terminal 1 cable 2.5...35 mm² - cable stiffness: solid
      Power circuit : screw clamp terminal 2 cable 16 mm² - cable stiffness: flexible - with cable end
      Complementary
      network frequency
      50/60 Hz
      mounting mode
      Fixed
      mounting support
      Rail
      Plate
      mounting position
      Vertical
      Horizontal
      thermal protection adjustment range
      40...63 A conforming to IEC 60947-4-1
      phase failure sensitivity
      Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
      [Ue] rated operational voltage
      600 V AC 50/60 Hz conforming to CSA C22.2 No 14
      600 V AC 50/60 Hz conforming to UL 508
      690 V AC 50/60 Hz conforming to IEC 60947-2
      [Ui] rated insulation voltage
      690 V conforming to IEC 60947-2
      [Ith] conventional free air thermal current
      63 A conforming to IEC 60947-4-1
      network frequency
      50/60 Hz conforming to CSA
      50/60 Hz conforming to IEC 60947-4-1
      50/60 Hz conforming to UL
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947-2
      power dissipation per pole
      8 W
      mechanical durability
      30000 cycles
      electrical durability
      30000 cycles on AC-3 at 440 V In/2
      maximum number of switchings
      25 cyc/h
      rated duty
      Continuous conforming to IEC 60947-4-1
      tightening torque
      5 N.m - on EverLink BTR screw connectors - cable 2.5...3.5 mm²
      5 N.m - on EverLink BTR screw connectors - cable 2.5...16 mm²
      breaking capacity
      Icu 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
      Icu 100 kA at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
      Icu 15 kA at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
      Icu 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
      Icu 4 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
      [Ics] rated service short-circuit breaking capacity
      100 % at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
      100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
      100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
      50 % at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
      60 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
      height
      120 mm
      width
      61 mm
      depth
      113 mm
      product weight
      0.7 kg
      Environment
      standards
      EN 60947-2
      BS EN
      NF EN
      DIN EN 60947-2
      IEC 60947-4-1
      EN 60947-4-1
      IEC 60947-2
      DIN EN 60947-4-1
      product certifications
      CSA
      UL
      LROS (Lloyds register of shipping)
      protective treatment
      TC
      IP degree of protection
      IP20 open mounted conforming to IEC 60529
      IP55 in enclosure conforming to IEC 60529
      shock resistance
      22 gn 20 ms conforming to IEC 60068-2-27
      vibration resistance
      2.5 gn 0...25 Hz conforming to IEC 60068-2-6
      ambient air temperature for operation
      -20...60 °C open mounted
      -20...40 °C in enclosure
      ambient air temperature for storage
      -40...80 °C
      fire resistance
      960 °C conforming to IEC 60695-2-1
      operating altitude
      <= 3000 m
      resistance to mechanical impact
      0.5 J
      Contractual warranty
      Warranty period
      18 months
    • Documents & Downloads

      Language
      • English
      Catalogue
      Date
      Size
      Add to My Documents
      TeSys GV - Catalogue 2017 - Motor circuit breakers
      Product environmental
      Date
      Size
      Add to My Documents
      Date 23/05/18
      Size 379.7 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    Nos conseillers sont disponibles pour répondre à vos questions de 8h00 à 18h00 du lundi au vendredi toute l'année.