140ARI03010C Product picture

Range: Modicon Quantum

Harsh environment

140ARI03010C

140ARI03010C Product picture
Range: Modicon Quantum

Harsh environment

140ARI03010C

analog input module Modicon Quantum - 8 I Ni / Pt 100, 200, 500, 1000

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Analogue input module
    Complementary
    analogue input number
    8
    input type
    Differential
    addressing requirement
    9 input words
    analogue input type
    Temperature probe - 100...450 °C Pt 100, Pt 200, Pt 500, Pt 1000
    Temperature probe - 200...850 °C Pt 100, Pt 200, Pt 500, Pt 1000
    Temperature probe - 60...180 °C Ni 100, Ni 200, Ni 500, Ni 1000
    Temperature probe 0.5 mA Ni 100, Ni 200, Ni 500, Ni 1000
    Temperature probe 2.5 mA Pt 100, Pt 200, Ni 100, Ni 200
    analogue input resolution
    13 bits
    input impedance
    >= 10 MOhm
    absolute accuracy error
    0.1 °C
    linearity error
    +/- 0.01 % full scale
    +/- 0.5 °C
    accuracy drift according to temperature
    +/- 0.5 °C at 25 °C
    +/- 0.9 °C at 0...60 °C
    isolation between channels and bus
    2500 V DC for 60 s
    1780 V AC 47...63 Hz for 60 s
    isolation between channels
    300 Vrms AC
    update time
    1200 ms 3 wires
    640 ms 2 wires/4 wires
    fault type
    Broken wire
    Overtacking scale
    marking
    CE
    local signalling
    1 LED green bus communication is present (Active)
    1 LED red external fault
    8 LEDs green channel is turned on
    8 LEDs red channel fault
    bus current requirement
    200 mA
    power dissipation in W
    1 W
    module format
    Standard
    product weight
    0.3 kg
    Environment
    protective treatment
    Conformal coating Humiseal 1A33
    standards
    CSA C22.2 No 142
    UL 508
    product certifications
    CUL
    FM Class 1 Division 2
    resistance to electrostatic discharge
    4 kV contact conforming to IEC 801-2
    8 kV on air conforming to IEC 801-2
    resistance to electromagnetic fields
    10 V/m 80...1000 MHz conforming to IEC 801-3
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    relative humidity
    95 % without condensation
    operating altitude
    <= 5000 m
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    Catalogue
    Date
    Size
    Add to My Documents
    Certificate
    Date
    Size
    Add to My Documents
    Date 6/08/18
    Size 233.4 KB
    Date 19/06/18
    Size 363.5 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 19/06/18
    Size 233.5 KB
    Date 6/08/18
    Size 510.4 KB
    End of life manual
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
    RoHs Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    RTD Input 8-Channel Module
    Wiring Diagram