140AIO33000 Product picture
Discontinued

Range: Schneider Legacy Products

Industry

140AIO33000

140AIO33000 Product picture
Discontinued
Range: Schneider Legacy Products

Industry

140AIO33000

intrinsically safe analog output module Modicon Quantum - 8 O

Show more characteristics >
140AIO33000  has not been replaced. Please contact your customer care centre for more information.

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Intrinsically safe analog output module
    software designation
    Concept V2.2 and above
    ProWORX
    Unity Pro
    Complementary
    product destination
    In conjunction with products for zone 20, 21 or 22
    analogue output number
    8
    analogue output range
    0...20 mA 0 to 20000 points
    0...25 mA 0 to 25000 points
    4...20 mA 15 bits, 0 to 16000 points
    4...20 mA 15 bits, 0 to 4095 points
    loop resistance
    <= 500 Ohm
    absolute accuracy error
    +/- 0.2 % of full scale at 25 °C
    accuracy drift according to temperature
    <= 70 ppm/°C
    40 ppm/°C
    linearity
    +/- 1 LSB
    update time
    4 ms
    setting time
    1 ms to +/- 0.1 % of the final value
    isolation between channels and bus
    1780 Vrms for 60 s AC
    fault type
    Open circuit 4...20 mA
    power dissipation in W
    12.5 W
    hot swapping fallback
    Not allowed per intrinsic safety standards
    protection type
    Internal fuse
    marking
    CE
    II1 G/D-EEx ia IIC
    bus current requirement
    2.5 A
    module format
    Standard
    product weight
    0.3 kg
    Environment
    standards
    CSA C22.2 No 142
    Directive ATEX 94/9/EC
    EN 50014
    EN 50020
    EN 50039
    EN 50281-1-1
    EN 50284
    UL 508
    dust zone
    Outside zone
    product certifications
    C-Tick.1
    FM Class 1 Division 2
    Hazardous location class 1, division 1 groups A, B, C
    SIRA 02ATEX2345X
    resistance to electrostatic discharge
    4 kV contact conforming to IEC 801-2
    8 kV on air conforming to IEC 801-2
    resistance to electromagnetic fields
    10 V/m 80...2000 MHz conforming to IEC 801-3
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    relative humidity
    95 % without condensation
    operating altitude
    <= 5000 m
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    End of life manual
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    Intrinsically Safe Analog Output Module
    Cenelec Certified Wiring Diagram



Nos conseillers sont disponibles pour répondre à vos questions de 8h00 à 18h00 du lundi au vendredi toute l'année.