Australia

Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

140AII33010 Product picture
Discontinued

View all Schneider Legacy Products

Schneider Legacy Products - 140AII33010

Industry

140AII33010 Product picture
Discontinued
View all Schneider Legacy Products
Schneider Legacy Products - 140AII33010
Industry

intrinsically safe current input module Modicon Quantum

Show more characteristics >
140AII33010  has not been replaced. Please contact your customer care centre for more information.
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Intrinsically safe current input module
    software designation
    Concept V2.2 and above
    ProWORX
    Unity Pro
    type of filter
    Single low pass input filter -3 dB 15 Hz +/- 20 %
    Complementary
    product destination
    In conjunction with products for zone 20, 21 or 22
    analogue input number
    8
    analogue input range
    0...20 mA
    0...25 mA
    4...20 mA
    analogue input resolution
    0...16000 counts 4...20 mA
    0...20000 counts 0...20 mA
    0...25000 counts 0...25 mA
    0...4095 counts 4...20 mA
    absolute maximum input
    25 mA internally limited
    input impedance
    100 Ohm +/- 0.1 %
    absolute accuracy error
    +/- 0.05 % typical of full scale at 25 °C
    +/- 0.1 % of full scale maximum at 25 °C
    accuracy drift according to temperature
    +/- 0.0025 % typical of full scale/°C
    0.005 % maximum of full scale/°C
    linearity error
    0.003 % of full scale
    common mode rejection
    > 100 dB 50/60 Hz
    update time
    750 ms
    isolation between channels and bus
    2500 V for 1 minute DC
    1780 V 47...63 Hz AC
    fault type
    Broken wire 4...20 mA
    power dissipation in W
    7.5 W
    hot swapping fallback
    Not allowed per intrinsic safety standards
    protection type
    Internal fuse
    marking
    CE
    II1 G/D-EEx ia IIC
    bus current requirement
    1500 mA
    module format
    Standard
    product weight
    0.3 kg
    Environment
    standards
    CSA C22.2 No 142
    Directive ATEX 94/9/EC
    EN 50014
    EN 50020
    EN 50039
    EN 50281-1-1
    EN 50284
    UL 508
    dust zone
    Outside zone
    product certifications
    C-Tick
    FM Class 1 Division 2
    GOST
    SIRA 02ATEX2345X
    resistance to electrostatic discharge
    4 kV contact conforming to IEC 801-2
    8 kV on air conforming to IEC 801-2
    resistance to electromagnetic fields
    10 V/m 80...2000 MHz conforming to IEC 801-3
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    relative humidity
    95 % without condensation
    operating altitude
    <= 5000 m
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    End of life manual
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    Intrinsically Safe Current Input Module
    Cenelec Certified Wiring Diagram



Nos conseillers sont disponibles pour répondre à vos questions de 8h00 à 18h00 du lundi au vendredi toute l'année.