FAQs

Ask a Question

Electromagnetic emissions characteristics of Canalis and Iline Busduct Systems

Please find below magnetic induction values at 1 meter. These values are simulated from a model, created and adjusted on some real measures.

Range & rating    Magnetic induction value at 1m (µT)
KSA100    0,23
KSA160    0,39
KSA250    0,64
KSA400    0,99
KSA500    0,66
KSA630    0,82
KSA800    1,04
KSA1000    1,20
KTA800    0,31
KTA1000    0,46
KTA1250    0,63
KTA1600    0,90
KTA2000    1,23
KTA2500    1,63
KTA3200    2,06
KTA4000    2,98
KTC1000    1,11
KTC1350    1,40
KTC1600    1,54
KTC2000    0,39
KTC2500    0,58
KTC3200    0,80
KTC4000    1,13
KTC5000    1,54

As a reminder, magnetic induction values are inversely proportional to the square of the distance from the busway. At a distance of less than 1 meter, the allocation of electromagnetic emissions is not uniform.
 