False Micrologic P alarms are being recorded and appearing in PME 7.2

These are false alarms and can be removed, but requires editing the Micrologic.evt file.

The process is as follows:
- Find the Micrologic.evt file located in C:\Program Files (x86)\Schneider Electric\ION Enterprise\system\translators\events\micrologic.evt
- Edit the file
- In the following 2 lines: 14 and 15 if they are 'Yes', make them 'No'.
- Save and close the file


 