Do we have a MCCB selection chart for the Fire Pumps?

Yes, We have a MCCB selection chart for the Fire Pumps. Based on the AS/NZ3000/7.10.9.2 the MCCb can handle, 
1) 125% FLC holding continuously. 
2) 600% FLC for for 20 seconds
3) 1250% FLC Inrush. 

See the attachment for reference. 