How much power can be regenerated into the supply system by ATV680?

The ATV680 is able to regenerate 100% nominal power continuously and 120% for 60 sec every 10 min when regenerative mode is enabled. With the factory setting (CLIG = LHM) the drive allows just 10% braking power.
Set ([Complete settings] -> [Generic functions] -> [Active Front End] -> [AFE Generator Mode]) CLIG to LHRM or 120.0% to enable full braking power.

 