How to use Twido Comm Macro to read/write values with Modbus addresses beyond %MW data range?

The range of %MW for Twido is -32768 to 32767,it can't be changed.
So if you want to input an address value larger than 32767,you can input the minus value whose binary type equals to the number you want.
For example,if you want to input 50300 (2#1100010001111100) you can just input -15236 whose binary type is 1100010001111100 too.