How to connect NSX circuit breaker to the Modbus/Ethernet Netowrk?

The Micrologic of the NSX Circuit breaker has only ULP communication. So you require a Modbus or Ethernet Interface to put the NSX Circuit breaker in the Modbus/Ethernet Network.
Attached Modbus/Ethernet architecture connection drawing for the NSX circuit breakers. 
Part No. Reference: 
Modbus Interface Device - IFM - TRV00210
Ethernet Interface Device - IFE - LV434011 or LV434010

Ref: FAQ FA315869  for NW/NT Circuit breakers