FAQs

Ask a Question

How many iEM3265 Energy meter with BAC net communication protocol can be put in a one network?

The unit load (based on specification of internal component used) is 1/8th, but because of design & application margins and environmental factors, we strongly recommend that the maximum number of devices (nodes) connected directly in one branch be limited to 32. 
It greatly reduce the chances of communication issues.
Was this helpful?
What can we do to improve the information ?