Is it Possible to Upgrade a 1600A NW16 Breaker to a 2000A NW20 by Changing the Sensor Plug.

No. It is not possible. As per the attached document the NW16 have sensor rating only from 800 - 1600A, So a 2000A Sensor Plug is not suitable for NW16 Breaker. So it can not be changed. 