Issue:
What is the address of the command word of the ATS48? Product Line:
Altistart 48 Environment:
All serial numbers
Cause:
N/A Resolution:
The Modbus command word address for the ATS48 is 400. However, Modbus requires an offset. If the controller does not have a built in offset, then the actual value you would enter would be 401.