What can cause an Err5 fault on the S-Flex ATV212 drives?
Issue:
What can cause an Err5 fault on the S-Flex ATV212 drives?
Product Line:
Altivar ATV212 S-Flex
Environment:
All with an serial coms setting turned on.
Cause:
Started to get the Err5 fault after setting F829 to Lowworks control
Resolution:
Err5= is a serial communications error. If you program F829 to be controlled over the network make sure you are sending a signal within the programmed timeout period.
Check timeout setting on F803
Check the remote HMI cable if they used.
Check the F829 settings try setting F829 back to 1 to see if it will clear the Err5.