FAQs

Ask a Question

ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?

Issue:
ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?

Product Line: 
Altivar ATV61 and ATV71

Environment:
All types

Cause:
The control supply voltage is to incorrect.

Resolution:
Check the control supply voltages between +24vdc and com or +24V and 0V. 
If using an external supply check +24Vdc supply connect between P24 and 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.
Was this helpful?
What can we do to improve the information ?