What is the Software Filter Time for TM2/TM3 Analog I/O Modules in Somachine Basic?

Software filter time parameter for TM2/TM3 analog input module is the time constant of the 1st order filter (or the time to reach 63% of the final value).

Take following config as example, for 4...20mA signal, it will take 20ms for the signal to change from 4mA to 12.6mA (20mA x 63%).

 